The fuel bills are abnormally high
Info
Published
July 10, 2009
Subscribe to RSS feed
If you want to save fuel, fix the air vents. Take them off and try to blow through them. If they're clogged, boil them in vinegar for an hour. If they still don't work, replace them.
Check the firing rate of the burner as well. You should be firing to the boiler's connected load (the piping and radiation) and no more. If your burner is too large it will raise the system pressure very quickly, and then shut off on the pressuretrol.
If you combine an oversized burner with clogged air vents you'll magnify the problem - and you'll increase the fuel bills. If the burner is oversized it will also throw water up into the system. That leads to wet steam, and wet steam can also make the burner short-cycle. The pressure builds quickly as the steam leaves the boiler and confronts the air. But because there's so much water in the steam, the steam quickly condenses, and that makes the burner come on again.
Short-cycling wastes fuel. Find the cause and eliminate it.
When steam traps are not working, fuel bills soar. There is no substitute for steam trap maintenance in a steam heated building. Find the defective traps and repair or replace them.
You can check thermostatic radiator traps with a thermometer. There should be at least a ten-degree temperature drop from one side to the other. Float & thermostatic and bucket traps have no temperature drop across them. Check these by opening the line downstream of the trap. You should see mostly condensate with some flash steam come from the trap. If you see live steam, repair or replace the trap. Before you replace a bucket trap, make sure it's primed with water. If a bucket trap loses its prime, it will blow live steam.
Think for a minute about a high/low-fire burner. You begin with the big flame because both the insulated pipes and the radiators are cold. The big flame lets' you drive steam out to the ends of the mains. Since the piping represents at least one-third of the total load, you need that big flame on start-up. But once you've made the insulated piping hot, the burner can drop to the low-fire setting because the insulated piping's ability to condense steam has lessened.
Now imagine you start with the little flame instead of the big flame. Can you imagine how difficult it will be to push steam to the furthest radiator? This is why you should never undersize burners. If the burner is too small, the fuel bills will be very high. Always fire to the connected load.
And since a lot of steam goes up the chimney, you wind up with the same effect you'd have if the burner was undersized. It runs on and on, but the furthest radiators never get hot.
To check for a hole, flood the boiler up into the header piping. You'll know you have a problem if you see water pouring out of the boiler's jacket. By the way, if you have an automatic water feeder, it pays to install an inexpensive water meter on the feed line. Keep a log of the meter reading and you'll have an early warning of a system leak or a hole in the boiler.
Some control manufacturers use a pressuretrol to figure out when steam fills the piping and radiation. It's easy to trick these pressuretrols. All it takes is a bit of dirt either in the pressuretrol or the pigtail. If the fuel bills are high, check that pressuretrol and pigtail.
Other heat-timing devices use thermistors to sense temperature rather than pressure. Usually, you place the thermistor at the end of the longest steam main, but there are no fixed rules. It varies from building to building. However, if the thermistor is on a main that has a clogged air vent, the burner will run all the time. That's because the trapped air will keep the steam from reaching the thermistor. Check, too, for thermistors that wind up on cold water lines, drain lines and, yes, even gas lines!
If you have a gravity-return system, make sure the thermistor is high enough on the main. It needs to be below the "A" or "B" Dimension so the rising condensate doesn't cover and cool it. (See The Lost Art of Steam Heating for a complete discussion of "A" and "B" Dimensions.)
Check to make sure you have the thermostat properly calibrated. And use an ammeter when you're checking. Don't guess at that anticipator setting.
If the thermostat has a mercury switch, make sure the thermostat hangs level on the wall. See if cold drafts hit the thermostat, or if it's hanging on a poorly insulated, outside wall. All these things lead to higher-than-normal fuel bills.
A great investment you can make in any steam system is to install a stack thermometer in the breeching. Keep a log showing the stack temperature. Start the log right after you've cleaned the boiler thoroughly. When you see the temperature rise, you know it's time to clean the boiler again.



