The condensate- or boiler-feed pump doesn't behave as it should
Info
Published
July 10, 2009
Subscribe to RSS feed
Someone should clean the strainer at the end of each heating season, but unfortunately, most strainers get cleaned only when there's a problem. If the strainer should clog, little or no condensate will return to the receiver. The condensate pump won't run often enough to replace the water in the boiler. If there's an automatic water feeder on the boiler, it will feed to keep the burner firing. But returning condensate, unable to get through the strainer, will back into the mains and cause water hammer.
Clean the strainer.
The strainer's job is to protect the pump from this sediment. However, if the strainer isn't working (someone may have removed the screen, for instance) particles of rust will work their way into pump's mechanical seal and cause a leak.
If the condensate pump has a packing gland instead of a mechanical seal (older pumps do), the sediment can cause the gland to leak too much. If you overtighten the packing nut to slow the leak, you might damage the pump's shaft.
Clean the system with trisodium phosphate, and make sure the strainer is clear.
This can happen in an open system (such as a steam system) when the water is close to the boiling point. When the impeller spins, the pressure at its inlet drops. The too-hot water flashes into a vapor and expands tremendously. The vapor bubbles then move quickly toward the edge of the impeller where the pressure is high. The higher pressure collapses the vapor bubbles. When that happens, water surrounding the collapsed bubble rushes into to fill the void. This water moves at an incredible speed. It hits the metal at the edge of the pump's impeller with such force that it quickly erodes the metal and causes the pump to fail.
To solve the problem, repair the defective traps. Don't try to cure the problem with a single "master" trap at the inlet to the condensate pump. Get to the root of the problem by repairing the steam traps.
Ideally, the pH of a steam system should range between seven (neutral) and nine (mildly alkaline). If the pH gets too low or too high it can affect the ceramic part of the pump's mechanical seal and cause the pump to leak.
Check the water's pH with litmus paper and adjust it with chemicals if necessary.
Most condensate pump manufacturers set their standard pumps to discharge at 20 psi. This is good for a low pressure system that can operate up to 15 psi (15 psi + 5 psi = 20 psi). Some condensate pumps, however, are built to order and may have pumps that discharge at a lower pressure. If the pump's pressure can't overcome the boiler's pressure, the pump can't return the condensate to the boiler.
Lower the boiler pressure (if that makes sense), or increase the head pressure of the condensate pump (by replacing it).
Unfortunately, sludge will often build up in the return line and clog the check valve, keeping it from closing tightly. Make sure you clean that strainer on the condensate- or boiler-feed pump's inlet.
If the check valve doesn't seat tightly, water from the boiler will back up into the receiver, raise the float switch and start the pump. So if you find your condensate- or boiler-feed pump is starting and stopping all the time, take a close look at that check valve. The easiest way to test it is to close the service valve at the inlet to the condensate pump. That will stop the flow of water into the pump's receiver. If the pump continues to cycle on and off, you know the water is coming from the boiler.
Isolate the check valve and clean it out.
Now and then, however, the float will work its way off the end of the float rod. When that happens, the pump stops operating because it no longer has a way of knowing where the water is. Usually, the condensate rises up in the receiver's vent or overflow line and floods the boiler room, but don't depend on this. From time to time, a float ball will come off the end of a float rod and work its way into the vent line. If this happens, you might not see the water overflow. Some manufacturers weld a baffle across the vent line inside the tank to keep this from happening.
To check for a missing float ball, operate the float switch by hand. You'll feel the resistance if the float ball is still on the end of the float rod. If it feels too loose, remove the float switch and replace the ball.
You can cure the problem by installing a vacuum breaker anywhere in the near-boiler piping or in the boiler itself. Just make sure the vacuum breaker winds up between the boiler water line and the motorized valves.
Another problem with a "master" trap is that it will release condensate at steam temperature. Much of that hot condensate will flash back into steam as it enters the receiver, causing further problems with the pump.
Remove the "master" trap, and repair the defective traps throughout the system.
If you're having a problem with the motor, check the voltage. If necessary, use a recorder to track any changes in voltage over time. Notify the power company of what you've found.
If it's that hot in the boiler room, there's also a good chance you're also not getting enough combustion air to the burners. And keep in mind, some modern boilers draw their combustion air from duct work attached directly to the burner. With little fresh air entering the room, the ambient temperature can get very hot, very fast. Bring in fresh air to cool the room.
On a gravity-return system, the wet return connects to the boiler's equalizer at a point about two inches below the lowest operating point (this varies from manufacturer to manufacturer so you should always check their installation instructions).
When you have a condensate pump, you no longer have a gravity-return system. Should a return spring a leak, the boiler water can't back out of the boiler because of the condensate pump's check valve. Should the check valve fail, boiler water will back into the condensate pump. The pump will turn on and pump the water back into the boiler. Should the check valve and the condensate pump fail simultaneously, water will back into the pump's receiver and rise up the vent piping. Since this piping is usually several feet higher than the boiler's water level, the water still can't get out. If there's an overflow pipe in the vent line, however, the condensate can back out of the boiler should both the pump and check valve fail. In this case, a Hartford Loop would help on a pumped return system. But other than that, the Loop may cause problem. Water under pressure from the pump can splash up into the boiler header and create water hammer.
If this is your problem, relocate the pump's discharge line to the bottom of the boiler's equalizer.
Check the impeller for sludge or other debris by removing the pump from the volute.
Other people try to deal with the problem by plugging the receiver's air vent. They figure what they don't see can't hurt them. They're wrong because a condensate pump's receiver can't take much pressure. If you plug the vent, the receiver can explode. That's right, explode.
Another problem is that with a plugged vent line, air can't escape from the system, and condensate will have a tough time making its way back to the boiler room. Now and then, a float ball will come off the end of a float rod and work its way into the vent line. Some manufacturers weld a baffle across the vent line inside the tank to keep this from happening.
If you find a plugged vent line, clear it immediately.
Try raising the water line to within an inch of the top of the gauge glass. If the water in the boiler is clean it will not surge over the top of the gauge glass. If it does, clean the boiler with trisodium phosphate.
Also, make sure you're not overfiring the boiler. If you are, correct it by firing only to the connected load.
If you use the #150 on a low-pressure boiler, however, the bellows will lengthen, and by doing so, shorten the vertical distance between the "pump-on" and "low-water cutoff" points. Working at low pressure, your burner may shut off on low-water before the boiler-feed pump has a chance to bring the level up to where it should be.
To avoid (or solve) this problem, order McDonnell & Miller's #150MD controller instead of their #150 if you have a low-pressure boiler. The "MD" stands for "maximum differential." It's the same control, but McDonnell & Miller sets the "MD" while they have it filled with low-pressure steam. Low-pressure steam doesn't compress the bellows as much, so you wind up with a wider, vertical distance between the "pump-on" and "low-water cutoff" points.
Don't try to adjust the factory settings of the mercury switches. If you do, you may void the manufacturer's warranty.
You'll find a float-operated automatic feed valve in the receiver of most boiler-feed pumps. The feeder's job is to make sure water always fills the lower quarter of the receiver. Typically, these float-operated valves can close off against a city water pressure of about 30 psi. If the city water pressure is higher than that, the valve will pass water, although the valve is supposed to be shut at that point. This can lead to a flooded boiler if the water rises up into the receiver's vent line (static pressure pushes water into the boiler). If there's an overflow line on the vent, you'll spill water either on the floor or down a drain.
If you're having this problem, install a pressure-reducing valve on the supply line going to the automatic feeder. Use the same sort of PRV that you would use to fill a hot water heating system.



