The air vents spit or make a hissing noise
Info
Published
July 10, 2009
Subscribe to RSS feed
Take a good look at the system and clean or replace the clogged air vents.
Every one-pipe steam system needs a main vent near the end of each main, but not right at the end in a tee. If the main vent is at the end of the main, water hammer might damage it. Place the vent at least 15 inches back from the end of the main, and up on a six-inch nipple. This gets it of the way of any water hammer damage. If you vent the mains properly, the steam will travel more evenly through the piping system, and leave more slowly through each vent. That increases the life of the vents, and lessens the spitting and hissing problem.
With a large radiator, however, you're better off using two slower air vents instead of one quick one. Drill and tap the radiator for the second vent a few inches below the first vent. The two vents will work together when the steam first reaches the radiator. Then, when the steam reaches the first vent (the higher of the two) the second will continue to vent at a slower rate. Since there will be less air in the radiator at that point, the second vent will be properly sized. This is a Dead Men's trick that works wonders!
Size and fire a boiler to the connected load. No more, and no less.
Increase the size of the air vents, or use several main vents on a manifold near the end of each main.



