There's no heat in part of the system
Info
Published
July 10, 2009
Subscribe to RSS feed
Open the top of the trap and examine the bellows. If it's cool and fully distended, the trap has probably failed in the closed position. If the system is running when you remove the top of the trap, notice whether air rushes from the radiator. This is another good indication that the trap has failed in the closed position.
Repair or replace the trap.
The trap's job is to pass air into the return side (the no-pressure) of the ladder, to close when steam arrives, and to reopen when condensate forms. If a trap fails in the open position, steam will pass into the return side of the "ladder," causing water hammer as it meets the condensate. Repair or replace the steam traps.
If the traps are defective, they'll mask this problem because there will be enough pressure to force the condensate out of the water leg. A lot of water hammer usually accompanies this evacuation of the water. That encourages the building owner to have his traps fixed. When you fix the traps he'll have no heat because the air can't get out. At this point, you have two choices. Raise the return line to eliminate the water seal, or install main vents at the outlet side of the end-of-main F&T traps.