Steam is coming out of the condensate- or boiler-feed receiver vent
Info
Published
July 10, 2009
Subscribe to RSS feed
Find the failed traps and repair or replace them.
Remember, the steam traps are in the building to create the points of pressure and no pressure. If the system could operate with a single "master" trap, the Dead Man who installed the system would have done it that way.
Another problem with a "master" trap is that it will release condensate at steam temperature. Much of that hot condensate will flash back into steam as it enters the receiver, causing further problems with the pump.
Remove the "master" trap, and repair the defective traps throughout the system.
Check the size of the trap against the load and the pressure differential. If it's oversized, replace it.